hepa air filtration system cost

Cost of HEPA Air Cleaning Systems Quality Better - value grade Labor Unlicensed - handyman Job Complexity Direct fit replacement Get an instant, no-obligation estimate of HEPA Air Cleaning System options and costs in your zip code. Our calculators have been updated for 2016 to reflect current fair costs and options for HEPA Air Cleaning Systems. Just enter your options and zip code above - then select "Update". HEPA Air Cleaning Systems - Pricing and Installation Cost Notes Homewyse cost estimates are approximate ranges for basic work in typical conditions. The estimates should only be used for preliminary planning. Homewyse estimates are NOT substitutes for quotes from qualified vendors. Homewyse strongly recommends that you contact reputable professionals for an accurate assessment of work required and costs for your project - before making any decisions or commitments. Labor tasks - Modify air handling system to connect unit inline. Connect and seal unit.

Mount and connect transformer to nearby, existing 120V receptacle. The homewyse cost estimates include all typical costs for removal and disposal of existing unit, hardware and components needed to connect, secure and properly operate and service the HEPA cleaning unit.
air purifier monthly payments The homewyse HEPA Air Cleaning System cost estimates do not include costs for new installation of, repairs to, or relocation of existing ducting, electrical connection, fuel supply line and exhaust vent systems.
2014 harley touring air cleanerCosts associated with permit acquisition and sign off are not included.
holmes hepa type air purifier small Higher priced HEPA Air Cleaning Systems may include features/attributes that include higher capacity and improved filtration.

HEPA Air Cleaning System installation costs are commonly quoted from a standard rate and can be estimated/quoted by the service professional after measurement and visual inspection at the job site. The variation in installation costs for complex configurations (non-rectangular shape, many corners, multiple levels, etc.) can be considerable. For accurate cost estimates, collect detailed bids from several qualified professionals. To maximize the payback of your HEPA Air Cleaning System investment, use materials and installation quality appropriate for your home and neighborhood - but be careful not to over improve. Less expensive alternatives to HEPA Air Cleaning Systems may provide a better return on investment. Reduce total project cost by having multiple vendors bid on the same, detailed work specification of your HEPA Air Cleaning System project. Save on installation costs by combining similar jobs and by being willing to have your project completed during low demand periods for the vendor/installer.

HEPA Air Cleaning System - Project Cost References Benchmarking Productivity Indicators for Electrical and Mechanical Projects The Journal of Construction Engineeringa nd Management, Jul 2002, The HUD PATH Rehab Guide Volume 8: HVAC/Plumbing U.S. Department of Housing and Urban Development Office of Policy Development and Research, Mar 2011, Editorial Staff How to Size HVAC Systems Correctly Pacific Northwest National Laboratory, Dec 2009, Editorial Staff HVAC - Heating, Ventilating, and Air Conditioning, Third Edition Amer Technical Pub; 3rd edition, May 2003, S. Don Swenson, ISBN 826906788 Unit Pricing Data: AC Wholesalers HVAC Products and Supplies AC Wholesalers, Jun 2016, Website Unit Pricing Data: Alpine Home HVAC Products Alpine Home, Jun 2016, Website Unit Pricing Data: Younits HVAC Products and Supplies Younits, Jun 2016, Website Unit Pricing Data: Home Depot HVAC Products and Supplies Home Depot, Jun 2016, Website Unit Pricing Data: Lighting and Ceiling Fan Pricing Westside, Jun 2016, Website

HEPA Air Cleaning System - Related Items IAQ Article Use Policy In the past, air filtration systems in spaces such as offices and schools were designed primarily to protect HVAC equipment and reduce the need for facility cleaning. In recent years, people have become aware of the issue of indoor air quality as independent studies have focused attention on the deleterious effects of airborne contaminants and the relationship of “sick building syndrome” to higher absenteeism and lower productivity. In turn, facility executives have felt increasing ethical, legal and marketing pressures to provide a high-quality indoor air environment for their occupants. Air filtration systems aim to capture, in a cost-effective manner, as many of the suspended particulates, biological materials and gases from the air as possible. An air filtration strategy depends on the building’s occupancy, location, specific air quality issues, and the type and operation of the HVAC system.

For example, the strategy for an airport terminal, which is subject to high volumes of diesel and jet fuel gases, differs from that of a typical office building. Filters are rated based on a minimum efficiency rating value (MERV). Normal filter types range from low efficiency (MERV 8) to medium efficiency (MERV 13) to high efficiency (MERV 15). (See box on page 14.) MERV 13 or MERV 15 filters are effective for most commercial and institutional applications. Facility executives should balance air filtration efficiency with operating cost, which basically comprises filter costs and the cost of electricity to power the air handling system. Low-efficiency filters cost approximately $50 each. High-efficiency filters cost roughly $140 each. HEPA filters range in cost from $180 to $500 each. Pressure drop is one of the factors in the operating cost equation. Pressure drop is the measurement, in inches, of the decrease in air flow through the filter compared to no filter. Pressure drop is affected by MERV, dust loading and fan velocity.

The higher the MERV, the greater the pressure drop across the surface of the filter. Similarly, as the filter accumulates particles, the pressure drop increases, resulting in decreased air flow through the filter. For example, at the recommended velocity of 500 fpm, the initial pressure drop of a new filter when the fan is running at maximum velocity is approximately 0.35 to 0.75 inches for a MERV 13 filter, 0.85 to 1.0 inch for a MERV 15 filter, and 1.0 to 2.0 inches for HEPA filters. It might seem that the higher the MERV rating, the higher the operating cost because of the higher initial and replacement costs of the filters, plus the cost of power to operate the higher horsepower fans required to push the air through the filters. But it’s more complicated than that. Consider a comparative analysis of operating costs for medium efficiency versus high efficiency filters in a commercial office building. Most office buildings use variable air volume systems, and, depending on the building’s location, fans operate, on average, at 70 to 90 percent volume.

The filters are at their highest pressure drops at maximum volume, thus the difference in operating costs between medium-efficiency and high-efficiency filters will be greater in a building in which the fans average 90 percent volume than in a building in which fans average 70 percent. Regardless of the efficiency of the filter, operating cost is quite specific to the building; there is no rule of thumb. This means the type of filter should be selected based on the specific building location, occupancy, air quality issues and type and operation of the HVAC system. However, it is reasonable to specify a filter of at least MERV 13 to maintain good indoor air quality in common types of spaces. At 85 percent efficiency, the pressure drop is generally less than 0.50 inches, which can be handled by most existing air handling systems. If an owner is considering a higher efficiency system, a life-cycle analysis is strongly recommended to compare benefits against increased operating costs.

High-efficiency-particulate air (HEPA) and ultra-low-penetration air (ULPA) filters have efficiencies ranging from 95 percent at 0.3 microns to more than 99.99999 percent at 0.12 microns. HEPA filters are widely used to control allergens and microbes in hospitals and laboratories, in sensitive manufacturing facilities and in facilities requiring protection from agents of bioterrorism. ULPA filters were developed in the early 1960s for use in the microelectronics manufacturing industry, where they are still used today. Typically, a HEPA or ULPA filtration system uses lower efficiency filters as “pre-filters” to capture some of the particulates before the air reaches the final stage of filtration. That setup extends the life of these expensive filters. Carbon filters, which adsorb odors and gases, are primarily used in airports and highly specialized industrial applications. They are not only expensive, but also have a very high pressure drop, so they are limited to applications with a maximum air flow of 200 fpm.

This requires mechanical units to be sized accordingly, that is, 2.5 times larger. Electrostatic filters create an electrical charge in the air, causing particles to attach not only to the filter, but also to one another, forming heavier particles that drop out of suspension. These are effective in controlling allergens and tobacco smoke, but care must be taken to specify a type that does not generate ozone, which is harmful to the respiratory system. These are rarely used in commercial applications because of increasingly common bans on smoking, but they are used in a number of large airports. Most modern Class A office buildings use filters rated MERV 13 or higher. Building owners realize that this translates to higher operating costs. However, they can market a high-quality indoor environment, justifying higher lease rates. At the same time, the owner’s potential liability drops. More schools should be equipped with MERV 13, if not MERV 15 filters, plus ultraviolet (UV) light sterilization because of children’s susceptibility to respiratory infections and the effects of pollutants.

UV units that emit type C light could be incorporated into the air handling system just behind the air filters, reducing biological pathogens both in the air and on the filters themselves. In contrast, because of the largely transient nature of the occupancy, most retailers tend to use lower efficiency air filtration systems, unless higher efficiency filters are required to protect their merchandise. Health care facilities are a special case. Hospital codes require HEPA filtration for critical areas, such as operating rooms, other invasive procedure rooms, infectious disease isolation rooms and emergency room waiting areas. Ali Sherafat, P.E., is a senior vice president in the Los Angeles office of Syska Hennessy Group, a consulting, engineering, technology and construction firm. Basics of Air Filtration In the past, the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) standards defined air filter efficiency as the percentage of airborne particles larger than 1 micron captured by a filter;

for example, 30 percent, 80 percent or 95 percent. The new ASHRAE Standard 52.2 — which defines the MERV scale — assigns a value for the filter’s minimum efficiency in capturing particles at six progressive stages of dust-loading with particles in the range of 0.3 to 10 microns. Comparing the new standard with the old, for example, a filter rated MERV 8 will capture roughly 30 percent of 1-micron particles at maximum dust-loading; MERV 13, 80 percent; and MERV 15, more than 95 percent. A filtration system consists of a filter frame, filter pack, separators, filter media and sealants. Media are the filtering materials, usually paper, that is pleated to increase surface area and fit into the desired space. Separators support the filter media and provide channels through which the air can flow to reach the filter. The filter pack contains the media and separators. Sealants create a leak-proof seal between the filter pack and the filter frame, which contains the whole assembly.